    VL Flow Switch

    • MOQ100 Piece
    • Medium temperature-20..+100°C
    • Tolerance±5 % of full scale value
    • Switching voltageMax. 230 V AC
    • Pressure resistancePN 10 bar
    • Supply TypeExporter, Supplier
    • Preferred Buyer Location All over the world
    View More Details
    Send Enquiry

    Company Information

    • calendar Member Since 8 Years
    • building Nature of Business Retailer
    • gst icon GST No. 24CXWPP9877P1ZT

    Ask for more detail from the seller

    Contact Supplier
    Report incorrect details
    • Product Details

    • Company Details

    no_img_icon

    • MakeHonsberg
    • Switching voltageMax. 230 V AC
    • Tolerance±5 % of full scale value
    • Medium temperature-20..+100°C
    • MediaWater (oils, gases and aggressive media available on request)
    • Ambient temperature-20..+70°C
    • SwitchReed switch
    • Process connectionFemale thread G 1/2..G 1
    • Pressure resistancePN 10 bar
    • Non-medium contact materialsPC, PA, NBR, nickelled brass
    • Protection class2 - safety insulation
    • ConnectionPlug DIN 43650-A / ISO 4400
    • Switching current1 A
    • Switching capacity50 VA
    • Nominal widthDN 15..25
    • Ingress protectionIP 65
    • Weight0.02 kg

    Feature : Optionally switching contact
    Characteristics : A piston moves in a transparent glass tube, relative to the flow. The position of the float depends on the volume flow (weight force versus resistance to flow), and indicates the flow rate on the scaled glass tube.
    Handling and operation :

    • Include straight calming section of 5 x DN in inlet and outlet
    • When tightening the union nut, the connection piece must be countered using an open-ended spanner (SW 19).
    • If the media are dirty, install a filter (use magnetic filter for ferritic components).
    • It must be ensured that the values given for voltage, current, and power are not exceeded.
    • When switched on, a load must be connected in series.
    • The electrical details apply to ohmic loads. Capacitive and inductive loads must be operated using a protective circuit.


    Options :

    • Display and switching ranges for oil or gas
    • Special values
    • Scale 0..100 %
    • Optionally transformer 250 V AC, 1,5 A, 50 VA, Wiring no. 0.282


    Ordering information :

    • Specify direction of flow, medium, and switching range.
    • For oils, state viscosity, temperature and designation (e.g. ISO VG 68) (enquire about range).
    • For gases, state pressure (relative or absolute), temperature and medium (e.g. air) (enquire about range).


    Download


    Download Detail File : Click Here
    Interested in this product? Ask for more details & Latest Price from seller
    Send Enquiry
    Share your requirements for a quick response!
    Tell us what you need?

    By clicking Get Quotes Now, I accept the T&C and Privacy Policy.

    Looking for VL Flow Switch?

    Quantity
    Seller Contact Details
    Waiting for permission
    To search by voice, go to your browser settings and allow access to microphone

    Allow microphone access to search with voice