Contact SupplierWe have parted our infrastructure into several units and one of them is warehouse wherein we keep a huge stock for furnishing urgent and quick requirements of the clients. Buyers can order our products in bulk, as we maintain year around availability. In addition, we have reliable transportation system to make timely delivery.
ESTAdry / ESTAprop ACMKP capacitors
ACMKP Series - Low – Voltage Power Factor Correction Capacitors
Application
Standards |
IEC 60831-1+2, EN 60831-1+2, IS 13340 |
---|---|
Approvals |
UL, ULc , BIS |
Over-voltages |
Ucn + 10 % (up to 8 hours daily), Ucn + 15 % ( up to 30 minutes daily) |
Tolerances on capacitance |
±5% |
Routine test voltage, terminal/terminal |
2.15 x Ucn, AC, 2 seconds |
Losses |
< 0.25 ....... < 0.45 W/kVAr |
Degree of protection |
IP20 (terminal cover for higher protection, class |
Permitted casing temperature |
Max. 65°c (measured on top of the can) |
Cooling |
Naturally air-cooled |
Permissible relative humidity |
Maximum 95% |
Maximum allowed altitude |
2000 m above sea level |
Mounting position |
Vertical and horizontal |
Mounting and grounding |
Threaded M 12 stud at the bottom of the container, max. torque 1 0 Nm |
Safety features |
ALL-PHASE over pressure tear-off fuse (irreversible current interruption), self-healing film technology |
Casing |
Aluminum |
Dielectric |
Polypropylene film, self-healing |
Filling agent |
Dry (gas filled) and oil filled |
Over-current |
1.5 X IN |
---|---|
Inrush current |
200 x IN |
Life expectancy |
≥ 115 000 operating hours |
Routine test voltage, terminal/casing |
3000 VAC, 10 seconds |
Ambient temperature category |
-25/D |
Over-current |
1.8 X IN |
---|---|
Inrush current |
250 x IN |
Life expectancy |
≥ 130 000 operating hours |
Routine test voltage, terminal/casing |
4800 VAC, 2 seconds |
Ambient temperature category |
-25/D |
Over-current |
2.5 X IN |
---|---|
Inrush current |
300 x IN |
Life expectancy |
≥ 150 000 operating hours |
Routine test voltage, terminal/casing |
4800 VAC, 2 seconds |
Ambient temperature category |
-25/70oC |