Contact SupplierWe Offer Tap Position Transducer.
This transducer is used for measurement of the mechanical position of an external device or equipment. The mechanical position of the external device (Transformer Tap Change Gear) is converted to a resistance value with a potentiometer or a resistor network by a rotary switch arrangement. The output (which is a load independent current or voltage) is proportional to the ratio of the resistance value at a position (tap) to the maximum resistance value in the network [i.e. resistance value at the maximum position (tap)]. The output can be connected directly to indicating instruments, data transmission system, Computer systems or SCADA systems.
Feature
• High accuracy, withstands wide temp variation
• Wide range of Input / Output to meet National / International requirements.
• Complies to revised IEC 60688-(1997-10) standards.
• Flexibility in auxiliary power supply requirements - A.C. / D.C.
• Rugged and vibration resistant.
• Withstands seismic test as per IEC 344-1974 for Nuclear Power applications.
• Available in dust proof sheet plastic enclosures suitable for Back panel / Din rail mounting.
• Multiple outputs also available - upto 4.
• High input / Output isolation - 4.0 KV.
• Display Optional.