Contact SupplierIn Mains Supply mode-it allows unrestricted supply to the load.
In Generator Supply mode – Its electronic circuit will continuously monitor the load/current. As the current value exceeds the preset value for more than 7-8 sec. (T 1) , Current Limiting Device will trip the power supply for predetermined time 10-30 sec.(T 2) & then it will switch ON the power supply again & start Monitoring the load current again & the whole process will restart.
Lockout cycle for overload limiter will be 5-10 cycles.(optional/user defined).
TIMER-T 1 | To surpass surge current/initial inrush current of connected load e.g. Tv, refrigerator, fan etc.. | Very useful to avoid unnecessary switching |
TIMER-T 2 | Provide delay time in switching on the power supply after overload condition | Very useful to avoid relay chattering & also gives positive switching to the relay contacts |
TIMER-T 3 | To provide time delay to avoid switching on all the loads simultaneously | Very useful to avoid overloading of the generator at its start up time. |