Company Information
Ask for more detail from the seller
Contact SupplierThe name of our company figures in the list of the prominent Exporters and Suppliers of Steel Conduit Pipes. Our Conduit Pipes are designed and fabricated using the finest grade mild steel. Owing to our rich experience in this domain, we have been able to provide Steel Conduit Pipes that deliver excellent performance in the toughest conditions. Our Steel Conduit Pipes are manufactured in compliance with IS: 9537 [Part II] 1981 standards. We stock Steel Conduit Pipes in a various thicknesses, diameters and tolerances. We are glad to proclaim that our reputed company deals in ISI marked Steel Conduit Pipes. Our panel of well-versed quality controllers thoroughly tests and inspects the raw materials, goods in process and the finished products.
Highlights :
Benefits :
Nominal size of conduit (mm) | Outer diameter (mm) | Tolerance in outer diameter (mm) | Wall thickness of conduit pipes (mm) |
---|---|---|---|
20 | 20 | -0.3 | 1.4 to 1.8 |
25 | 25 | -0.4 | 1.4 to 1.8 |
32 | 32 | -0.4 | 1.4 to 1.8 |
40 | 40 | -0.4 | 1.6 to 2.2 |
50 | 50 | -0.5 | 1.6 to 2.2 |
At JPC, the quality control engineer and his team, inspect and test the raw materials, goods in process and the finished goods on daily basis. The following tests are conducted.
Name of the test | Methodology & Reasoning |
---|---|
Inspection of surfaces & Edges | Visual Examination (By Normal or conrrected vision without magnification). |
Inspection of Marking | Brand name, Nominal size & country of origin on each length. |
Dimensional check | For maximum OD by GO Gauge & minimum OD by NO Go gauge to maintain standard size. |
Wall Thickness Measurements | Measured with the help of vernier callipers as specified in BIS standard (Accuracy equal to or more than 0.02 mm). |
Compression testing machine | By compressing the samples on compression test apparatus & calculating the percentage compression as maintained in BIS 9537 part I & II. To assures the mechanical strength of conduits. |
Bend test and ball test | By bending the sample on bend test apparatus & testing the samples for deformity & cracking of protective coating of original material. To check the ease of flow of the wire within the pipe |
Screw Thread Test | Length of the thread is measured by vernier & profile of thread by Go & NO Go gauge this ensures smooth jointing of pipes with each other. |
External influence (protective coating) | With the help of chemical as prescribed in BIS : 9537 Specifications medium and high protective coating of rigid steel conduits are tested for adequate protection against external influences. |
Durability of Marking | By rubbing process |
Specification Dimensional Requirements as per IS:9537 (Part-II)
Nominal Size In mm | 20 | 25 | 32 | 40 | 50 |
Outside diameter (mm) | 20 | 25 | 32 | 40 | 50 |
Tolerance on outside diameter(mm) | -0.3 | -0.4 | -0.4 | -0.4 | -0.5 |
Minimum outside diameter (mm) | 19.7 | 24.6 | 31.6 | 39.6 | 49.5 |
Wall Thickness | |||||
(a) Minimum (mm) | 1.4 | 1.4 | 1.4 | 1.6 | 1.6 |
(b) Maximum (mm) | 1.8 | 1.8 | 1.8 | 2.2 | 2.2 |
Maximum capacity of JPC Brand Rigid Steel Conduits For Drawing PVC Insulated Cables Conforming to IS:694-1990
Size of Cable | Size of Conduit | ||||
20 mm | 25 mm | 32 mm | 40 mm | 50 mm | |
Nominal Size in Mm | Number of Cables | ||||
1.5 | 4 | 6 | 10 | --- | --- |
2.5 | 4 | 6 | 10 | --- | --- |
4 | 3 | 5 | 10 | --- | --- |
6 | 2 | 3 | 7 | 14 | --- |
10 | --- | --- | 5 | 11 | --- |
16 | --- | --- | 3 | 7 | --- |
25 | --- | --- | --- | 4 | 6 |
35 | --- | --- | --- | 4 | 6 |
50 | --- | --- | --- | 3 | 5 |