Contact SupplierThe Resin Cast Cts Are Normally Used For Indoor Application Inside The Panels .the Resign Cast Cts Can Be Used For Outdoor Application Also Provided It Is Enclosed In A Hermetically Sealed Metal Tank
Construction Features :
type: Resin Cast. Outdoor. Oil Minimum | ||||||
Nominal System Voltage (kv) | LT CT | 11 | 33 | 66 | 132 | |
Highest System Voltage (Kv) | 0.66 | 12 | 36 | 72.5 | 145 | |
Power Frequency withstand voltage( 1 min Kv) | 3 | 28 | 70 | 140 | 275 | |
impulse withstand voltage (KvP) | NA | 75 | 170 | 325 | 650 | |
Rtaed Burden | 2.5 VA to 30 Va | |||||
Rated frequency (Hz) | 50 | 50 | 50 | 50 | 50 | |
Creepage Distance Phase To Earth (m.m) | NA | 300 | 900 | 1815 | 3625 | |
Rated Primary Current | 2.5 AMP to 2000AMp | |||||
Rated Continous Thermal Current (Amp)MAx | NA | 125 %of Rated Primary Current | ||||
Rated Secondary Current | 1 Amp 5 AMP/s Per Client Requirment | |||||
Rated Short time Thermal Current | NA | 3KA to 40 KA for one three Second | ||||
Rated Dynamic current(KA Peak) | NA | 2.5 times of short time current | ||||
Accuracy class | NA | 0.2S,0.2,0.5s,0.5,1.0 for metering ,10 PS and PS for protection | ||||
Rated Instrument security Factor | 0.5,, 1.0 | less than 5 year | ||||
Rated Accuracy limit Factor | 10,20,30 | |||||
Knee Point Voltage | As per Customer requirement |