Contact SupplierWe are offering vacuum feed gas chlorination system.
Motive water (water at high pressure) passes through the injector to produce vacuum. This vacuum extends upto automatic vacuum regulator (avr). The chlorine gas supplied (from tonnes cylinders or chlorine evaporators) under pressure is reduced to a lower pressure by pressure reducing value [prv] and to a constant vacuum at the avr. The gas under vacum passes through a gas or rotameter and flow control valve [fcv].
a differential pressure regulator[dpr] is provided for chorinators above 6 kgshr capacity, to control the pressure drop across the flow meter and also to ensure accurate and steady flow of gas. The chlorine gas then gets mixed with the water at the injector and is the discharged to the point of application. Safety valves like check valve, emergency drain valve, pressure relief valve and vacuum relief valve are provided in this system to make it safe for both operating personnel and equipment's longevity.