Contact SupplierMacroplast manufactures Potential transformers with top tank (expansion chamber) upto 132 Kv system voltage. This design has two tanks. The core and windings are contained in the lower tank. The prima, winding is taken through the HT insulator to be connected to the primary terminal arranged on the top tank. The secondary windings are connected to secondary terminals placed on the lower tank. In this design, the .Top Tank provides space for expansion of Oil.
Construction Features :
type: Resin Cast. Outdoor. Oil Cooled | |||||
---|---|---|---|---|---|
Nominal System Voltage (kv) | 11 | 33 | 66 | 132 | 220 |
Highest System Voltage (Kv) | 12 | 36 | 72.5 | 145 | 245 |
Power Frequency withstand voltage( 1 min Kv) | 28 | 70 | 140 | 275 | 460 |
impulse withstand voltage (KvP) | 75 | 170 | 325 | 650 | 1050 |
Rtaed Burden | 10 VA TO 500VA | ||||
Rated frequency (Hz) | 50 | 50 | 50 | 50 | 50 |
Creepage Distance Phase To Earth (m.m) | 300 | 900 | 1815 | 3625 | 6125 |
Rated secondary voltage | |||||
R.ted voltage factor | 110 Volt 110√3 Volt | ||||
Accuracy class (IS/IEC standard) | 1.2 Cont G 1.5 for 30 Second | ||||
0.2,D.5,1.0 For Metering ¢ 3P,5P, 6P For Protection |