Contact SupplierLOAD OPERATED FAST RESPONSE REACTIVE POWER COMPENSATION SYSTEM : –The system is designed to work automatically on highly variable, fluctuating, unbalanced utility loads. The compensation is done on percentage of load current settable on site with the help of variable setting pot on Controller with fast response with cutoff of set value of power factor with another pot.
Load operated Automatic power factor correction system mainly
suitable to Lighting loads, Agriculture pumps, Welding loads, Lifts, Crane, Injection Molding Machines. It is a highly Fast response system designed to measure & operate to connect & disconnect the required Kvar Capacitors to achieve Target power Factor with reference to load current.
LED Indications:-
High Voltage - RED LED
Low Voltage - RED LED
Power Factor - YELLOW LED
Lead PF - RED LED
Low Load PF- RED LED
Power ON - GREEN LED
Bank ON - GREEN LED
LED Indications Details:-
High Voltage LED glows when system
voltage is 1.15 times of rated voltage.
Low Voltage LED glows when system
voltage is 0.7 times of rated voltage.
Current LED glows when system current is above set limit.
Current - YELLOW LEDLead P.F. LED glows when power factor is leading.
Bank ON LED glows when contactor
switches ON capacitor bank.
Power ON LED glows when power is
switched ON.
LL LED glows when load current is
below 1% of rated transformer Current.