    Fire Survival Test Apparatus As Per BS

    • Fuse Box: 2 Amps Fuse box for 3 Phases and Neutral
    •  : Categories F2 / F30 / F60 and F120 as per BS 7846:2009
    • Test Chamber: Single walled chamber 3m x 3m x 3m (Optional)
    • Burner (For Protocol W and Z): 500 mm Long Ribbon Type Burner
    • Supply TypeManufacturer, Exporter, Supplier, Retailer
    • Preferred Buyer Location All over the world
    View More Details
    Send Enquiry

    Company Information

    • calendar Member Since 16 Years
    • building Nature of Business Retailer
    • Year of Establishment 1985

    Ask for more detail from the seller

    Contact Supplier
    Report incorrect details
    • Product Details

    • Company Details

    no_img_icon

    • Test Chamber: Single walled chamber 3m x 3m x 3m (Optional)
    • Transformer: 3 Phase variable power supply of 1KV capacity
    • Burner Stand: 200 mm above the test bench
    • Sample Stand: Made of SS with 5 rings to support the sample during the test.
    • Flame Temperature: Monitored using tow K type thermocouple
    • Tripping System: Individual Tripping System for 3 Phases, Neutral and Earth
    •  : Categories F2 / F30 / F60 and F120 as per BS 7846:2009
    • Fuse Box: 2 Amps Fuse box for 3 Phases and Neutral
    • Burner (For Protocol W and Z): 500 mm Long Ribbon Type Burner
    • Burner Control: Using Flow Meter and Pressure Regulator for Air and Gas
    • Load Bank: To Indicate continuity of 3 phases, Neutral and Earth
    • Burner (For Protocol C): 610 mm Long Tube Type Burner
    • Suitable For: Protocol C , W and Z as per BS 6387:2013

    Model Number: SSI 512 FSBS

    Standard Number: BS 6387 : 2013 ,BS 7846 : 2009 ,BS 8491 : 2008

     

    This instrument is designed to testing cables required to maintain circuit integrity when subject to fire alone where the test conditions is based upon a flame with a controlled heat output corresponding to a temperature of up to 950oC.

     

    Instrument Principle

    This instrument is designed to testing cables for resistance to fire of cable required to maintain circuit integrity under fire conditions. The instrument is applicable to cables of rated voltage not exceeding 600/1000 V and of overall diameter less than or equal to 20mm (as per BS 6387) and diameter exceeding 20mm (as per BS 7846).

    The instrument is designed

    Test cables under three protocols as per BS 6387:2013, BS 7846:2009 and BS 8491:2008 for

    Protocol C: subject the cable under test to a flame via direct impingement corresponding to a temperature attach of 950oC

    Protocol W: subject the cable under test to a flame via direct impingement corresponding to a temperature attach of 650oC with direct application of water simulating a sprinkler system.

    Protocol Z: subject the cable under test to a flame via direct impingement corresponding to a temperature attach of 950oC with indirect application of mechanical shock.

    Category F2: Resistance to Fire, Resistance to fire with water, resistance to Fire with Mechanical Shock assessed separately as per BS 6387

    Category F30: Resistance to Fire with direct mechanical impact and water assessed in combination when tested as per BS 8491:2008 for 30 min

    Category F60: Resistance to Fire with direct mechanical impact and water assessed in combination when tested as per BS 8491:2008 for 60 min.

    Category F120: Resistance to Fire with direct mechanical impact and water assessed in combination when tested as per BS 8491:2008 for 120 min.

    The instrument can be bought as complete unit or can be bought as piece meal as per customer requirement.

    Instrument

    The Instrument Consist of

     

    Burner (for Protocol C) : Tube Type LPG / propane  gas burner. Overall length of the nozzle is  610mm.
    Burner (for Protocol W and Z ) : Ribbon Type LPG / propane  gas burner. Overall length of the nozzle is  500mm.
    Burner Control: With double variable flow meters (Roto meter). Roto meters range is : 95+/- 5 LPM, gas flow range is : 10 +/- 0.5 LPM. Two Pressure Gauges of 0-60psi will be provided to control the input pressure for Air and Gas.
    Flame Temperature: Adjustable up to 950+/- 50oC using the flow control.
    Temperature Calibration : Two MI thermocouples will be provided to calibrate the flame temperature (can be fitted in each jig)
    Three Phase Transformer  (up to 1 KV) with individual tripping system for all the three phases, Neutral and Earth.
    Test Jigs for Test with Fire only : Sample stand complete with SS rings and sample holder for Test with Fire only as per BS 6387:2013
    Test Jigs for Test with Fire with Mechincal Shock : Sample stand complete hammer to produce mechanical shock during test for Test with Fire with mechanical shock as per BS 6387:2013
    Test Jigs for Test with Fire with water sprinkler : Sample stand complete water sprinkler to sprinkle water on the samle during fire test as per BS 6387:2013
    Test Jig for Test with Direct Machanical Shock in combination of water jet as per BS 8491:2008
    Load bank to indicate the line continuity for three phases, Neutral and Earth


    Interested in this product? Ask for more details & Latest Price from seller
    Send Enquiry
    Share your requirements for a quick response!
    Tell us what you need?

    By clicking Get Quotes Now, I accept the T&C and Privacy Policy.

    Looking for Fire Survival Test Apparatus As Per BS?

    Quantity
    Seller Contact Details
    Waiting for permission
    To search by voice, go to your browser settings and allow access to microphone

    Allow microphone access to search with voice