Products / Services
  • Products / Services
  • Companies
  • Buy Leads
    Post Buy Requirement

    Circuit Breaker

    • Supply TypeManufacturer, Exporter, Supplier, Retailer
    • Preferred Buyer Location All over the world

    Features Even in the event of a complete gas leak, our SF6 CBs are capable of breaking 100% normal current & with stand system voltage Advance warning of gas leak by continuous pressure....
    View More Details
    Send Enquiry

    Company Information

    • calendar Member Since 12 Years
    • building Nature of Business Retailer

    Ask for more detail from the seller

    Contact Supplier
    Report incorrect details
    • Product Details

    • Company Details

    no_img_icon

    Features

    • Even in the event of a complete gas leak, our SF6 CBs are capable of breaking 100% normal current & with stand system voltage
    • Advance warning of gas leak by continuous pressure monitoring
    • Explosion proof and fail-safe CB by means of safety membrane for each pole
    • Automatic safety shutters to cover live parts when CB is withdrawn
    • No degradation of main current carrying contacts, as there are separate currents carrying and arcing contacts
    • Our SF6 CBs operate at low pressure. The internal pressure rise at the instant of current interruption also stays low. Due to this, and the high degree of gas tightness, adequate for entire life of the breaker is ensured.

     

    Operating Mechanism
    • Proven spring operated mechanism
    • Designed to closed and latch
    • Manual/motorised option
    • In built trip free mechanism
    • In built anti pumping feature
    • Mechanical ON/OFF indication

     

     


      FP62DFP63GFP62DFP63GFP72DFP73D
    Rated Voltage kV 12 12 24 24 36 36
    Insulation level kVrms / kVp 28 / 75 28 / 75 50 / 125 50 / 125 70 / 170 70 / 170
    Rated Current A 1250 2500 1250 2500 1600 1600
    Braking Capacity kA 26.2 40 26.2 26.2 16 26.2
    Making Capacity kAp 65.5 100 65.5 65.5 40 65.5
    Short Time Current (1 or 3 Sec) kA 26.2 40 26.2 26.2 16 26.2
    Operating Sequence   O - 0.3 Sec - CO - 3 min - CO
    Auxiliary Switch Contacts   8NO + 8NC
    Spring Charging Motor Power W 250
    Spring Charging Motor Voltage V 230V AC, 110V DC, 220V DC
    Closing / Tripping Coil Power W 80
    Closing / Tripping Coil Voltage V 24, 30, 48, 110, 220DC
    Share your requirements for a quick response!
    Tell us what you need?

    By clicking Get Quotes Now, I accept the T&C and Privacy Policy.

    Looking for Circuit Breaker?

    Quantity
    Seller Contact Details
    Waiting for permission
    To search by voice, go to your browser settings and allow access to microphone

    Allow microphone access to search with voice