Applications  In order to maintain a fully charged battery, a constant voltage. The voltage is high enough to replace the self-discharge, but not as high as to cause excessive overhead. Although simply maintaining the output voltage is fixed relatively simple function, If the battery temperature is not compensated for the loss of the ability to occur during The temperature in the project and overloaded with the degradation of life is lower temperature.
TECHNICAL SPECIFICATION RATING Voltage 12 V, 24 V, 48 V, 110 V DC Current Upto 200 Amps INPUT Mains 230V(1Ø)/415V(3Ø) ± 15%, 50 Hz ± 6%AC Battery 45 to 600 Volts DC OUTPUT Load 45 to 600 V DC Charger Boost Mode : 1.2 times the battery voltage Float Mode : 1.08 times the battery voltage Regulation ± 1.5 Volts Ripple < 100 mV (peak to peak) with battery Overall Efficiency >70% under all conditions Charging Characteristic Constant current / Constant voltage / CVCC