Listing ID #5358647
Company Information
Ask for more detail from the seller
Contact SupplierSeries AVU Air Velocity Transmitter
ideal for building automation systems, ±5% or ±8% full scale accuracy
the seris avu air velocity transmitter is ideal for a wide range of hvac measurement and control applications, particularly in complete building control and energy management systems. The series avu transmitter operates by measuring the heat loss from one of the two sensing elements in the air stream, then calculating the air velocity. Units are virtually immune to drift due to the design of the sensing element,which makes the transmitter accurate over the whole air velocity range.
calibration option available under accessories.
product applications
supply and exhaust fan tracking,clean room systems,air pollution studies and manufacturing,zone control in hvac systems
modeldescription
avu-1-a-air velocity transmitter,range 0-785 fpm (0-4 m/s), 4-20 ma output.
avu-1-v-air velocity transmitter,range 0-785 fpm (0-4 m/s), 0-10 vdc output.
avu-2-a-air velocity transmitter,range 0-1575 fpm (0-8 m/s), 4-20 ma output.
avu-2-v-air velocity transmitter,range 0-1575 fpm (0-8 m/s), 0-10 vdc output.
avu-3-a-air velocity transmitter,range 0-3150 fpm (0-16 m/s), 4-20 ma output.
avu-3-v-air velocity transmitter,range 0-3150 fpm (0-16 m/s), 0-10 vdc output.
avub-1-v-air velocity transmitter,0-785 fpm (0-4 m/s) with 0-10 vdc output.
avub-2-v-air velocity transmitter,0-1575 fpm (0-8 m/s) with 0-10 vdc output.
avub-3-v-air velocity transmitter,0-3150 fpm (0-16 m/s) with 0-10 vdc output.
specifications
service:clean air and compatible,non-combustible gases.
accuracy:avu: ±5% of fs; avub: ±8% of fs.
response time (90%):5 sec (typical).
temperature limits:32 to 122°f (0 to 50°c).
humidity limit:0-90% rh,non-condensing.
power requirements:-a models 24 vdc +10%-15%;-v models 24 vdc or 24 vac +10% - 15%.
output signal:-a models 4 to 20 ma current loop;-v models 0 to 10 vdc.
loop resistance:(-a models ) 700 ω.
current consumption:60 ma + output current
maximum start up current:85 ma; 10 v
output current limit:(-v models) >10 ma
electrical connections:screw terminal. Cable gland for 4-8 mm wire (16 gage wire)
enclosure rating:nema 6 (ip67) except sensing point.
probe dimensions:9.45 x .75" (240 x 19 mm)
mounting orientation:unit not position sensitive. Probe must be aligned with airflow
weight:8.8 oz (250 g).
agency approvals:ce
features
4 to 20 ma or 0 to 10 v output versions,nema 6 (ip67) enclosure rating,ac or dc powered (loop version dc only),5% or 8% accuracy
model numberdescription
nistcal-av1nist traceable calibration certificate for air velocity thermal anemometer meters. note: equal certs will be charged per units purchased.
related products
series 641rm air velocity transmitter with remote probe,model vt120 integral vane thermo-anemometer,model vt-200 vane thermo-anemometer,technical reference books,model 8904 integral vane thermo-anemometer,model 471b thermo-anemometer test instrument
Weight : 8.8 Oz (250 G).
Material : Plastic
Usage : Non-combustible Gases.
Type : Air Velocity Transducer, Series AVU Air Velocity Transmitter
output : -A Models 4 To 20 MA Current Loop; -V Models 0 To 10 VDC.
Voltage : -A Models 24 VDC +10% - 15%; -V Models 24 VDC Or 24 VAC +10% - 15%.
Feature : Excellent Performance, High Quality
Power : -A Models 24 VDC +10% - 15%; -V Models 24 VDC Or 24 VAC +10% - 15%.
Condition : New
Warranty : 1yrs