Air Cooled steam vent condenser has been designed and fabricated using the guidelines from API 661 and ASME Section VIII Div 1. The MOC for tube bundle assembly SS 304 L and for structure carbon steel. Air cooled heat exchanger type is forced draft exchanger. Project Location :- Jorf Lasfer, Morocco Project Title :- Dap Plants 107 B & C Application :- Steam Vent Condenser DESIGN DATA:- Operating Fluid :- Steam Heat Load :- 3180.6KW Fluid In/ Out :- 103/100 º C Design Pressure :- 5.5 KG/CM2(A) Test Pressure:- 7.1KG/CM2(A) Design temperature :- 130ºC