Listing ID #3918398
Company Information
Ask for more detail from the seller
Contact SupplierEAPRO Pure Sine wave LB-UPS series UPS is designed to generate 3-phase 4 wire output by incorporating world’s most advanced DSP based 20 KHz Pulse Width Modulation technology to drive IGBT/MOSFET for increased crest factor. This type of UPS is widely used in lift, elevators, escalators, security systems, Water Pumps, Fire pumps etc. Whenever the utility supply is available, the charger provides constant voltage and constant current to charge the battery bank.
It consists of Sine wave three-phase UPS/ Inverter, battery charger, and an electronic change over module. EAPRO Pure Sine wave LB-UPS series UPS take cares your commercial and industrial equipments for their extended service life, as it is designed to suppress the harmonic distortion.Â
Closed Loop Auto Sensing Software Control (ASSC) Smart Charging circuit charges the battery for the enhanced battery life. It has the exclusive capability to provide longer power backup due to faster charging. EAPRO sine wave LB-UPS are of world class in terms of Performance, Durability, Reliability & Efficiency.
Application
DESCRIPTION |
4KVA |
5KVA |
6KVA |
8KVA |
10KVA |
12KVA |
15KVA |
20KVA |
25KVA |
30KVA |
40KVA - 70KVA |
70KVA - 100KVA |
|
Nominal Battery Voltage |
72 VDC |
72 VDC, 96 VDC |
72 VDC, 96 VDC, 120 VDC |
120 VDC |
180 VDC, 360 VDC |
180 VDC, 240 VDC, 360 VDC |
180 VDC, 276 VDC, 360 VDC |
276 VDC, 360 VDC |
360 VDC |
360 VDC |
360 VDC |
360 VDC |
|
AC MAINS MODE | |||||||||||||
Input Volt. {N-L} |
140V AC to 280 AC |
||||||||||||
Input Volt. {L-L} |
242V AC to 480 AC |
||||||||||||
Max Charging Current |
10A±1 A |
||||||||||||
Boost Charging Voltage |
14.4V +/-0.2V DC Per Battery (12V DC Each) |
||||||||||||
Trickle Charging Voltage |
13.7V +/-0.2V DC Per Battery (12V DC Each) |
||||||||||||
O/P Voltage (L-L) |
400V±2.5V AC |
||||||||||||
Full Load O/P Current/ Phase |
5.8± 0.5A |
7.3± 0.5A |
8.7± 0.5A |
12± 0.5A |
14± 0.5A |
17± 0.5A |
21.5± 0.5A |
23.5± 0.5A |
29.5± 0.5A |
34.9± 0.5A |
……. |
......... |
|
Low Battery Indication |
10.5V + 0.2V DC Per Battery (12V DC Each) |
||||||||||||
Change over time (For 3-ph inverters) |
<=40 milisec |
||||||||||||
Change over time (lift app.) |
<=30 sec |
BATTERY BACK-UP MODE | |
Output Wave Form |
Pure Sine Wave |
Output Power Factor |
0.8 |
O/P Voltage {N-L} |
230 ± 2.5 V AC |
Max. No load Batt. current |
0.9 ± 0.2 A |
Frequency |
50 Hz ± 1.0 Hz |
THD |
<3% |
O/P Voltage {L-L} |
400 VAC ± 2.5 VAC |
Full Load O/P current / Phase |
Same as AC Mains mode |
Low Battery Indication |
10.5 ± 0.2V Per Battery {12V Each} |
Display |
Welcome Message, Capacity, Output Voltage, Output Frequency, Load Percentage, |
Input Voltage and Frequency, Battery Charging, Battery Voltage, All Protections |
|
Protections |
Output Not Ok, Battery Voltage Low(4 Auto Retries), Over Load (6 Auto Retries) |
Input Voltage and Frequency, Battery Charging Voltage, All Protections |