Listing ID #4417607
Company Information
Ask for more detail from the seller
Contact SupplierDesigned for commercial usage, the PVI-10/12.5, three-phase inverter is highly unique in its ability to control the performance of the PV panels, especially during periods of variable weather conditions.
The high speed and precise Maximum Power Point Tracking (MPPT) algorithm provides real-time power tracking and improved energy harvesting.
Two independent MPPTs and efficiency ratings up to 97.8%
Highlights
Type code | PVI-10.0-TL-OUTD | PVI-12.5-TL-OUTD |
---|---|---|
Input side | ||
Absolute maximum DC input voltage (Vmax,abs) | 900 V | |
Start-up DC input voltage (Vstart) | 360 V (adj. 250...500 V) | |
Operating DC input voltage range (Vdcmin...Vdcmax) | 0.7 x Vstart…850 V (min 200 V) | |
Rated DC input voltage (Vdcr) | 580 V | |
Rated DC input power (Pdcr) | 10300 W | 12800 W |
Number of independent MPPT | 2 | |
Maximum DC input power for each MPPT (PMPPT, max) | 6500 W | 360...750 V |
DC input voltage range with parallel configuration of MPPT at Pacr | 300...750 V | 360...750 V |
DC power limitation with parallel configuration of MPPT | Linear derating from max to null [750 V≤VMPPT≤850 V] | |
DC power limitation for each MPPT with independent configuration of MPPT at Pacr, max unbalance example | 6500 W [380 V≤VMPPT≤750 V] the other channel: Pdcr-6500 W [225 V≤VMPPT≤750 V] |
8000 W [445 V≤VMPPT≤750 V] |
Maximum DC input current (Idcmax) / for each MPPT (IMPPTmax) | 34.0 A / 17.0 A | the other channel: Pdcr-8000 W |
Maximum input short circuit current for each MPPT | 22.0 A | |
Number of DC input pairs for each MPPT | 2 | |
DC connection type | PV quick fit connector 3) | |
Input protection | ||
Reverse polarity protection | Inverter protection only, from limited current source | |
Input over voltage protection for each MPPT | Yes | |
Photovoltaic array isolation control | According to local standard | |
DC switch rating for each MPPT (version with DC switch) | 25 A / 1000 V | |
Fuse rating (version with fuses) | 15 A / 1000 V | |
Output side | ||
AC grid connection type | Three-phase 3W+PE or 4W+PE | |
Rated AC power (Pacr @cosφ=1 ) | 10000 W | 12500 W |
Maximum AC output power (Pacmax @cosö=1) | 11000 W 4) | 13800 W 5) |
Maximum apparent power (Smax) | 11500 VA | 13800 VA |
Rated AC grid voltage (Vac,r) | 400 V | |
AC voltage range | 320...480 V 1) | |
Maximum AC output current (Iac,max) | 16.6 A | 20.0 A |
Contributory fault current | 19.0 A | 22.0 A |
Rated output frequency (fr) 3) | 50 Hz / 60 Hz | |
Output frequency range (fmin...fmax) 3) | 47...53 Hz / 57…63 Hz 3) | |
Nominal power factor and adjustable range | > 0.995, adj. ± 0.9 with Pacr =10.0 kW, ± 0.8 with max 11.5 kVA |
> 0.995, adj. ± 0.9 with Pacr =12.5 kW, ± 0.8 with max 13.8 kVA |
Total current harmonic distortion | < 2% | |
AC connection type | Screw terminal block, cable gland M40 | |
Output protection | ||
Anti-islanding protection | According to local standard | |
Maximum external AC overcurrent protection | 25.0 A | |
Output overvoltage protection - varistor | 3 plus gas arrester | |
Operating performance | ||
Maximum efficiency (hmax) | 0.98 | |
Weighted efficiency (EURO/CEC) | 97.1% / - | 97.2% / - |
Feed in power threshold | 30.0 W | |
Night consumption | < 1.0 W | |
Communication | ||
Wired local monitoring | PVI-USB-RS232_485 (opt.) | |
Remote monitoring | VSN300 Wifi Logger Card (opt.), VSN700 Data Logger (opt.) | |
Wireless local monitoring | VSN300 Wifi Logger Card (opt.) | |
User interface | 16 characters x 2 lines LCD display | |
Environmental | ||
Ambient temperature range | -25...+60°C (-13...+140°F) | -25...+60°C (-13...140°F) |
Relative humidity | with derating above 55°C (131°F) | with derating above 50°C (122°F) |
Sound pressure level, typical | 50 dBA @ 1 m | |
Maximum operating altitude | 2000 m / 6560 ft | |
Physical | ||
Environmental protection rating | IP65 | |
Cooling | Natural | |
Dimension (H x W x D) | 716 mm x 645 mm x 224 mm / 28.2” x 25.4” x 8.8” | |
Weight | < 41.0 kg / 90.4 lbs | |
Mounting system | Wall bracket | |
Safety | ||
Isolation level | Transformerless | |
Marking | CE (50 Hz only), RCM | |
Safety and EMC standard | EN 50178, IEC/EN 62109-1, IEC/EN 62109-2, AS/NZS 3100, AS/NZS 60950.1, EN 61000-6-2, EN 61000-6-3, EN 61000-3-11, EN 61000-3-12 |
|
Grid standard (check your sales channel for availability) | CEI 0-21, CEI 0-16, DIN V VDE V 0126-1-1, VDE-AR-N 4105, G59/3, C10/11, EN 50438 (not for all national appendices), RD 1699, RD 413, RD 661, P.O. 12.3, AS/NZS 4777, IEC 61727, IEC 62116, BDEW, MEA, NRS 097-2-1, VFR 2014 |
|
Available products variants | ||
Standard | PVI-10.0-TL-OUTD | PVI-12.5-TL-OUTD |
With DC switch | PVI-10.0-TL-OUTD-S | PVI-12.5-TL-OUTD-S |
With DC switch and fuse | PVI-10.0-TL-OUTD-FS | PVI-12.5-TL-OUTD-FS |