Our Products
Alarm Systems
2 Products availableElectric Circuit Components & Parts
1 Products availableAudio Recorders, Mixers & Transmitters
1 Products availableElectrical & Electronic Gadgets
1 Products availableSecurity And Inspection Devices
1 Products availableWindow
1 Products availableOur product range contains a wide range of Microcontroller Based Alarm Annunciator, PC Based Alarm Annunciator, Intrinsically Safe Alarm Annunciator, Miniature Alarm Annunciator and MIMIC Annunciation Panel
This Microcontroller Based Alarm Annunciator has been designed using microprocessor chip incorporated with cutting edge technology. These are widely in use and recommended by experts. We are wholesale retailers and our primary focus is on medium and bulk sized deliveries. If you have any queries, kindly contact our sales executives who can guide you further. Our prices are also fairly affordable.
We are a trusted manufacturer, exporter and supplier of PC Based Alarm Annunciator that is of excellent quality. They are supplied by us to our customers from locations near and far. We have used premium materials in making these alarm annunciators. The machines used to make them are also highly advanced with technical solutions embedded in them. Contact us if you are interested.
Our annunciators are compatible with PC. The data from annunciator located at a distance of upto 1.0km can be transferred through RS485 with suitable cable to PC located elsewhere i.e. in main control room, security cabin etc. away from the field. More than one annunciator also can be looped & connected to remote PC.
Model ISA-2 is an intrinsically safe alarm annunciator suitable for Group IIA, IIB or IIC application as per IS/IEC 60079-11:2006. This design is tested and certified by the only authorities in India viz. CIMFR-Dhandabad & CCOE-Nagpur. The Split type design comprises ofi) Intrinsically safe power supply unit suitable for SAFE AREA location andii) annunciator logic with LED display window located in Hazardous area.
IS annunciators are available for input supply of 24V DC OR 90 to 270V AC/DC supply. The available sequences are auto, manual or first out seq. The numbers of points per cabinet are four to Eighty points in various configurations. Three LEDs per window are provided, since filament lamps are obsolete & not permitted in Hazardous area location. Pneumatic hooter with flame proof solenoid valve is available for audible alarm in hazardous area location
Salient Features
Mounting & Installation Procedure :
Ensure the panel Cutout/s made for annunciator unit/s are as per drawing enclosed. Before installation check all sub-assemblies for transit damages if any. Install the Annunciator unit on the panel. Fix mounting clamps to secure the Annunciator unit in position. Check powerpack unit which is to be mounted separately in Safe Area. Fix the powerpack unit by means of screw and nuts. Remove the Annunciator Rear Cover and Powerpack Front Cover. Refer to external connection drawings for Annunciator & powerpack unit. Connect wire for pushbuttons to the Annunciator. Also interconnect Annunciator unit with powerpack unit as per external wiring diagram. Connect supply incoming and hooter cables to Powerpack Unit. Do not connect any signal contact cables. Proceed further as per ‘Testing Procedure’ given under : (3)
Possible Faults And Rectifiction
Rectification procedure for various possible faults which may occur,--- during commissioning, is given below: | ||
---|---|---|
No. | Fault Symptom | Rectification |
1 | Annunciator is totally off | a) Check input supply voltage. b) Check Power Supply Fuse. c) Open terminal plate & check wires for open conditions d) Follow standard fault finding procedure by checking filter capacitor, bridge rectifier diodes; transformer etc. |
2 | Flashing condition without audible for all modules. |
a) Check Hooter fuse, Hooter supply and Hooter itself. b) Check Audible Relay(located in power supply unit) for contact operation. c) Replace Flasher Module |
3 | Annunciator windows remain off (any one or more) | a) Check Supply output from power pack unit for those windows. b) Replace seq. Modules for those windows. c) Check LEDs by usinsg a multi-meter. |
4 | During Fault/Test operation for all windows LED remain steady on without flashing but Audible comes on. |
a) Replace flasher module. |
Note: If above mentioned Fault rectification procedure fail to solve the problem or the nature of the Fault is different from what is given above, then please write to us and furnish us the
following details.
1 to 8 PTS While ordering kindly furnish the following technical details:
Details :
Optional Features : available such as, additional relay, contact for repeat alarm available, site selectable trip/non trip alarm differentiation etc.Electrical Isolation : Electrically insulated from panel earth which automatically protects from electrical transients and shock hazard.
STANDARD WALLMOUNT ANNUNCIATORModel ANW-2103 is a small independent cubicle suitable for mounting on the wall, pump house, MCC or any other location where, free standing panels are not available.
It can meet for additional requirement of annunciator points, arise during commissioning or expansion programme. It is a self sufficient annunciator complete with facia windows, power supply unit, push button and hooter for audible alarm. The enclosure is suitable for outdoor locations in dust and weatherproof construction. Special type of enclosure for IP-54 or IP-55 also can be supplied. All the operational sequences and supply voltages given under ANA-2103 model are available with ANW-2103 model.