The company brings forth a remarkable range of
AMF Panel (Auto Mains Failure) for our esteemed customers. We hold specialization in designing AMF Panel in accordance with the international standards. AMF Panel, offered by the company, is applicable for managing DG sets. As a reliable Manufacturer, Supplier and Exporter, we manufacture AMF Panel up to 550 KVA. The AMF Panel is constructed out of the best quality 14/16 SWG thickness, high grade CRCA sheet steel. The AMF Panel, offered by us, is dust and vermin proof. Further, our AMF Panels are powder coated for longer life and are meticulously wired.
Highlights - A power circuit consisting of contactor, MCB and fuses
- Automatic start/stop of the generator in case of AC mains failure and its restoration respectively
- Facility of quick manual start/ stop
Logic - Mains Failure : 3-attempt engine cranking after mains failure else the engine fails to start. Engine starts-up within 10 sec of mains failure otherwise 2 more start pulses after every 10-15 seconds.
- Unhealthy Mains : Any of the phase failure or voltage drops below set value.
- Mains Restoration : Engine keeps running for 30 seconds before stopping, as mentioned by the Engine manufacturer.
Metering : One Ammeter with CTs & selector switch, one frequency meter, one voltmeter with selector switch and one hour meter.
Set of indications - Load on DG
- High water temp/high cylinder head temp
- Fault indications
- Overload
- LLOP
- Load on mains
Set of Push Buttons - Engine start/stop.
- Alarm acknowledge button for hooter.
- Reset button for fault indication.
Safety - High water temperature
- LLOP
- Overload tri
Battery Charger : A separate battery charger is provided for continuous charging of batteries in trickle/boost mode ensuring quick and easy starting of the engine.
Price : Ranging from Rs.50, 000 to 25 Lakhs