Gas Suppression Systems FM-200 (HFC-227EA) is a reliable solution based on HFC 227ea, an extinguishing agent known around the world. Built on 42-bar technology, these Gas Suppression Systems are efficient and space-saving. Whether for the valuable systems, data, people or the working environment, this Gas Suppression System provides optimum protection in case of fire and helps ensuring business continuity. The extinguishing agent of this Gas Suppression System is very effective and works at low extinguishing concentrations to protect people and assets. The extinguishing agent is chemically inert and has low electric conductivity. This Gas Suppression Systems provides ideal protection especially for areas with electrical and electronic risks of fire. Extinguishing without leaving any residue and without risking of corrosion is found in this Gas Suppression System- for example a smoldering fire in electrical switching rooms, telecommunication systems, data centers or server rooms can be checked before it spreads.
Features
Technical Specifications
Listings/Approvals
NAF® S 125 is a UL Recognized and US EPA SNAP Listed gaseous extinguishing agent. NAF® S 125 Engineered Systems are UL Listed.
NAF® S 125 is suitable for use in rooms, vaults, enclosed machines, containers, storage areas and wherever fixed enclosures are present. It is an electrically non-conductive media, it can therefore be used to protect electronic and delicate equipment. After discharge NAF® S 125 does not require the clean-up of the protected enclosure, making it extremely useful in applications where damage by other extinguishing methods would be prohibitive.
NAF® S 125 has a low order of toxicity. At typical design concentrations it can be safely used to protect normally occupied areas.
The NAF S 125® formulation includes a patented additive that reduces the levels of decomposition by-products normally generated by halocarbons during extinguishment and enhances extinguishing performance (inter alia US Patent No. 6, 402, 975 and EU Patent No. 630, 278).
By weight NAF® S 125 requires the lowest concentration, making NAF® S 125 the most cost effective clean agent solution available in the market today.
They are available in 180º and 360º coverage that is suitable for total flooding systems in occupied areas. This Gas Suppression System protects areas such as computers, archives, electrical and telecommunications equipment, Server Room/Data Center, Hospitals, Petrochemical, Offshore, Airport, Laboratories, Paint Booths, etc. The typical design concentration of this Gas Suppression System is 8%, with a discharge time of 10 seconds in accordance with the UL 2166 regulations.
Discharge is via valves that have been completely designed by manufacturer and certified by the top independent agencies. This gas suppression system offers great flexibility of adaptation to all actuation systems currently on the market, and even allows combinations of several of these. This gas suppression system design incorporates elements that protect against accidental activation due to micro-seepage. All of the valves are registered through the Ministry of Industry and thus comply with an obligatory standard. The NAF S125 extinguishing systems include discharge nozzles especially designed to maximize the properties of the extinguishing agent. They are available in 180º and 360º coverage.
Main benefits :
Certificates :
Physical Properties
Composition | HFC-125 + 0.15% of Limonene |
---|---|
Molecular weight | 120.0 |
Boiling point @ 1.013 bar | -48.3°C |
Density of the liquid @ 25°C | 1189.7 kg/m³ |
Critical temperature | 339.45 K |
Critical pressure | 3595 Kpa |
Vapor pressure @ 20°C | 12.09 bar |
Relative electrical resistance @ 1 atm. 21°C (N2=1.0) | 0.955 |
NFPA 2001 Edition 2012
Design concentration for Class A Fires | 8.7% (by volume) |
---|---|
Flooding factor for Class A Fires | 0.484 kg/m³ |
Design concentration for Class C Fires | 9% (by volume) |
Flooding factor for Class C Fires | 0.502 kg/m³ |
ISO 14520 Edition 2006
Design concentration for Class A/C Fires | 8.7% (by volume) |
---|---|
Flooding factor for Class A/C Fires | 0.484 kg/m³ |
PBPK (5 minutes exposure) | 11.5% |
Ozone Depletion Potential (ODP) | 0 |
Global Warming potential (GWP) | 2800 |